| Sign In | Join Free | My burrillandco.com |
|
| Ask Lasest Price | |
| Brand Name : | ABB |
| Model Number : | AI815 |
| Price : | Negotiations |
| Delivery Time : | 2-3 working days |
AI815 3BSE052604R1 I/O Modules - System 800xA hardware selector Digital I O Module
General info:
Type | Analog Input |
Signal specification | 0..20 mA, 4..20 mA, 0..5 V, 1..5 V |
Article number | 3BSE052604R1 |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | Yes |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Detailed data
Resolution | 12 bit |
Input impedance | 10 MΩ (voltage input) |
Isolation | Groupwise isolated from ground |
Under/over range | 0 / +15% |
Error | Max. 0.1% |
Temperature drift | Max. 50 ppm/°C |
Input filter (rise time 0-90%) | 290 ms |
Update cycle time | 10 ms |
Current limiting | Built in current limited transmitter power |
Maximum field cable length | 600 meters (656 yards) |
NMRR, 50Hz, 60Hz | > 40 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.5 W |
Current consumption +5 V Modulebus | 100 mA |
Current consumption +24 V Modulebus | Max. 265 mA (22 mA + 1.32 * transmitter current) |
Current consumption +24 V external | 50 mA |
Diagnostics:
Front LED’s | F(ault), R(un), W(arning) |
Supervision | Module error, if: analog read back, reference voltage, internal
power supply, checksum, watchdog and memory error |
Status indication of supervision | Module Error, Module Warning, Channel error |
| CE mark | Yes |
| Electrical safety | IEC 61131-2, UL 508 |
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
| Marine certification | BV, DNV-GL, LR |
| Protection rating | IP20 according to IEC60529 |
| Corrosive atmosphere ISA-S71.04 | G3 |
| Climatic operating conditions | 0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
| Pollution degree | Degree 2, IEC 60664-1 |
| Mechanical operating conditions | IEC/EN 61131-2 |
| EMC | EN 61000-6-4, EN 61000-6-2 |
| Overvoltage categories | IEC/EN60664-1, EN 50178 |
| Equipment class | Class I according to IEC 61140; (earth protected) |
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
| RoHS compliance | EN 50581:2012 |
| WEEE compliance | DIRECTIVE/2012/19/EU |
|